Overview
Introduction | IM and IMC are part of SM6 product range. This SM6 range is made up of modular units and used for the MV/LV substation in secondary distribution system up to 24 kV |
Application | IM is usually applied for incoming switchgear for on load switching. IMC is IM type cubicle with additional current transformer for measurement (for overload protection please consult us).
This IM or IMC is normally installed in the system with other part of SM6 product range such as QM, * auxiliary contacts QMC, CM, DM1, DM2, etc., in accordance with the design of a distribution system. |
Main
Basic Equipment | • SF6 Functional load break switch and earthing switch • Three phase busbar 630 A • CIT operating mechanism (IM & IMC) • Voltage presence indicators • Heater 50 W, 220 VAC • Three current transformers (IMC) • Connection pads for dry-type cables |
Condition Monitoring | • Basic : Thermal sensors (TH110) • Option : Humidity sensors (CL110) |
Options | • Motor for operating mechanism • Key-type interlocks • Release units (coil) • Operation counter • Visibility of main contacts • Pressure indicator device • Earth fault indicators • Digital ammeter • Surge arrester • Arc detection |
Physical
Colour | White (RAL 9003) |
Height | 170 cm – IM/IMC |
Width | 50 cm – IM/IMC |
Depth | 84 cm – IM/IMC |
Net weight | 120 kg IM – 200 kg IMC |
Electrical Characteristics
Rated Voltage | Ur | kV | 7.2 | 12 | 17.5 | 24 |
Insulation Level | ||||||
Insulation | Ud | 50/60 Hz, 1 min (kV rms) | 20 | 28 | 38 | 50 |
Isolation | Ud | 50/60 Hz, 1 min (kV rms) | 23 | 32 | 45 | 60 |
Insulation | Up | 1.2/50 µs (kV peak) | 60 | 75 | 95 | 125 |
Isolation | Up | 1.2/50 µs (kV peak) | 70 | 85 | 110 | 145 |
Rated voltage | Ur | kV | 7.2 | |
Breaking capacity | ||||
Transformer off load | A | 16 | ||
Cable off load | A | 31.5 | ||
Rated current | lr | A | 400 – 630 – 1250 | |
Short-time withstand current | lk/tk^(1) | kA/1 S | 25 | 630 – 1250 |
20^(2) | 630 – 1250 | |||
16 | 630 – 1250 | |||
12.5 | 400 – 630 – 1250 | |||
Making capacity (50 Hz) | lma | kA | 62.5 | 630 | NA |
50 | 630 | |||
40 | 630 | |||
31.25 | 400 – 630 |
Standards & Specification
IEC Standards | 62271-200 ,62271-1, 62271-103, 62271-105, 62271-100, 62271-102, 61869-2, 61869-3, 60044-8,
62271-206, 62271-304 |
UTE Standards for SM6-24 | NFC 13.100 NFC 13.200 NFC 64.130 NFC 64.160 |
EDF Specifications for SM6-24 | HN 64-S-41 HN 64-S-43 |
SEISMIC Standards for 24 kV | IEEE-693 2005 EN600068-3-3 1993 |
Environmental
Ambient air temperature | ≤40 °C ≤35 °C on average over 24 hours ≥-5°C |
Humidity | • Average relative humidity over a 24 hour period, ≤ 95% • Average relative humidity over a 1 month period, ≤ 90% • Average vapor pressure over a 24 hour period, ≤ 2.2 kPa • Average vapor pressure over a 1 month period, ≤ 1.8 kPa.For these conditions, condensation may occasionally occur. Condensation can be expected where sudden temperature changes occur in periods of high humidity.To withstand the effects of high humidity and condensation, such as breakdown of insulation, please pay attention on Civil Engineering recommendations for design of the building or housing, by suitable ventilation and installation. |
Ambient Air Pollution | No significant pollution by dust, smoke, corrosive and/or flammable gases, vapors or salt. |
Operating altitude | ≤ 1000 m > 1000 m, a derating coefficient is applied (Please consult us) |
Solar radiation | No solar radiation influence is permitted. |
Seismic (24kV & 36 kV) |
• Up to 0.5 g (horizontal) and 0.4 g (vertical) • Class 2 for 24 kV and Class 1 for 36kV • According to standards IEEE-693/2005 and EN 60068-3/1993 for the 24 kV and 36 kV |
Electro-magnetic compatibility | • Relays: 4 kV withstand capacity, as per recommendation IEC 60801.4 • Compartments: Electrical field: — 40 dB attenuation at 100 MHz — 20 dB attenuation at 200 MHz Magnetic field: 20 dB attenuation below 30 MHz. • According to standards IEEE-693/2005 and EN 60068-3/1993 for 36 kV (please contact us). |
Temperatures | The cubicles must be stored and installed in a dry area free from dust and with limited temperature variations. • For stocking: from -40°C to +70°C • For working: from -5°C to +40°C • Other temperatures, consult us. |
Protection Index | • Classes: PI (insulating partition) • Loss of service continuity classes: LSC2A (LSC1 for metering GAM/GBM functions) • Units in switchboard: IP3X • Between compartments: IP2X for SM6-24, IP2XC for SM6-36 • Cubicle: IK08 for SM6-24, IK07 for SM6-36. |
Monitoring
Continuous Thermal Monitoring | The power connections in the Medium Voltage products are one of the most critical points of the substations especially for those made on site like: • MV Cable connections Loose and faulty connections cause an increase of resistance in localized points that will lead to thermal runaway until the complete failure of the connections.Preventive maintenance can be complicated in severe operating conditions also due to limited accessibility and visibility of the contacts.The continuous thermal monitoring is the most appropriate way to early detect acompromised connection. |
Easergy TH110 Thermal Sensor | Easergy TH110 is part of the new generation of wireless smart sensors ensuring the continuous thermal monitoring of all the critical connections made on field allowing to: • Prevent unscheduled downtimes • Increase operators and equipments safety • Optimize and predictive maintenanceThanks to its very compact footprint and its wireless communication, Easergy TH110 allows an easy and widespread installation in every possible critical points without impacting the performance of the MV Switchgears.By using Zigbee Green Power communication protocol, Easergy Th110 ensure a reliable and robust communication that can be used to create interoperable solutions evolving in the Industrial Internet of Things (IIoT) age.Easergy TH110 is self powered by the network current and it can ensure high performances providing accurate thermal monitoring being in direct contact with the measured point. |
Packing Units
Unit Type of Package 1 | PCE |
Number of Units in Package 1 | 1 |
Package 1 Height | 190 cm |
Package 1 Width | 60 cm |
Package 1 Length | 120 cm |
Package 1 Weight | 145 kg |
Contractual warranty
Warranty | 12 Months |